NICET ITFAS-Level-1 Inspection and Testing of Fire Alarm Systems Level I Exam Exam Practice Test

Page: 1 / 9
Total 85 questions

Inspection and Testing of Fire Alarm Systems Level I Exam Questions and Answers

Question 1

Which three of the following branch circuit characteristics are required for circuit identification and accessibility of the fire alarm equipment's primary power supply? (Choose three.)

Options:

A.

The system circuit disconnect shall be permanently identified as "Fire Alarm."

B.

The system circuit disconnect shall be permanently identified at the control unit.

C.

Where a circuit breaker is the disconnecting means, a breaker locking device shall be installed.

D.

Where a circuit breaker is the disconnecting means, a breaker locking device shall be labeled.

Question 2

In a Class B initiating circuit, wires should be monitored for integrity by having a supervisory device connected to which of the following?

Options:

A.

Anywhere on the loop

B.

Beginning of the loop

C.

The first detector

D.

The last detector

Question 3

With all notification appliances operating, what is the maximum sound pressure level, combined with the ambient sound pressure level, at the minimum hearing distance allowed by code?

Options:

A.

100 dBA

B.

105 dBA

C.

110 dBA

D.

115 dBA

Question 4

How is a projected beam detector inspected?

Options:

A.

Check for obstruction

B.

Introduce smoke

C.

Remote test switch

D.

Use an optical filter

Question 5

Visible and audible trouble signals shall be indicated at which two of the following locations? (Choose two.)

Options:

A.

Alarm company office

B.

Emergency command center

C.

Fire alarm control unit

D.

Fire department headquarters

Question 6

When the main power is disconnected, how long should a power supply with emergency voice communication systems work in alarm mode?

Options:

A.

Maximum of 5 minutes

B.

Maximum of 15 minutes

C.

Minimum of 5 minutes

D.

Minimum of 15 minutes

Question 7

The minimum supervising station signaling requirement for a fire alarm system that monitors a sprinkler flow and tamper switch shall include which set of signals?

Options:

A.

Alarm, trouble, and phone line failure

B.

Alarm, trouble, and supervisory

C.

Alarm, trouble, supervisory, and daily test

D.

Alarm, trouble, supervisory, and primary power

Question 8

Which three of the following are types of fire alarm control units? (Choose three.)

Options:

A.

Central station

B.

Dedicated function

C.

Protected premises

D.

Releasing service

Question 9

An abnormal condition where a system, component, or function is out of order, and the condition can result in the system or unit not functioning when required is called which of the following terms?

Options:

A.

Impairment

B.

Intermittent

C.

Operational

D.

Supervisory

Question 10

Records of inspections, testing, and maintenance shall be provided in accordance with which section of NFPA 72?

Options:

A.

7.6.6

B.

7.8.2

C.

10.5.3

D.

14.6.3

Question 11

How often does a technician test the manual operation of a master box on a public emergency alarm reporting system?

Options:

A.

Monthly

B.

Quarterly

C.

Semiannually

D.

Annually

Question 12

How should the documentation cabinet be labeled?

Options:

A.

Fire alarm documents

B.

Fire alarm record documents

C.

System records

D.

System record documents

Question 13

According to NFPA 72, manual fire alarm boxes shall be located within which distance of each exit doorway on each floor?

Options:

A.

5 feet (1.5 meters)

B.

6 feet (2.0 meters)

C.

16 feet (5.0 meters)

D.

33 feet (10.0 meters)

Question 14

Secondary power for the fire alarm primary power supply shall be tested under which load?

Options:

A.

Half load

B.

Maximum load

C.

Minimum load

D.

Supervisory load

Question 15

What is the maximum travel distance between two fire alarm boxes measured horizontally on the same floor?

Options:

A.

30 feet (9.1 meters)

B.

60 feet (18.3 meters)

C.

90 feet (27 meters)

D.

200 feet (61 meters)

Question 16

What is the inspection frequency of supervising station alarm system transmitters?

Options:

A.

Monthly

B.

Quarterly

C.

Semiannually

D.

Annually

Question 17

Smoke detector activation in the ninth-floor elevator lobby shall activate which of the following functions?

Options:

A.

Alternate level recall

B.

Designated level recall

C.

Ninth-floor supervisory signal

D.

Ninth-floor trouble signal

Question 18

An off-normal signal shall be initiated during which of the following travel distances of the valve control apparatus from its normal position?

Options:

A.

1/5

B.

1/4

C.

1/3

D.

1/2

Question 19

Secondary power shall automatically provide power to a protected premises system within how many seconds after the primary power fails?

Options:

A.

10

B.

30

C.

60

D.

90

Question 20

In the event of power loss, how long shall a secondary power source for household fire alarm systems maintain operation?

Options:

A.

24 hours in the normal condition followed by 4 minutes of alarm

B.

24 hours in the normal condition followed by 9 minutes of alarm

C.

24 hours in the normal condition followed by 10 minutes of alarm

D.

24 hours in the normal condition followed by 60 minutes of alarm

Question 21

Notification appliances in a fire alarm system produce a distinctive evacuation signal that does which of the following?

Options:

A.

Alternates on for 1 second, off for 1 second

B.

Alternates on for 1 second, off for 1.5 seconds

C.

Provides a 3-pulse temporal pattern

D.

Provides a 4-pulse temporal pattern

Question 22

Which three of the following test methods are used to ensure that the smoke detectors are within their sensitivity range? (Choose three.)

Options:

A.

AHJ approved calibrated test

B.

Listed control equipment arranged for testing

C.

Manufacturer's calibrated sensitivity test instrument

D.

Test approved by the engineer

Question 23

What is the testing frequency of an engine driven generator?

Options:

A.

Weekly

B.

Monthly

C.

Semiannually

D.

Annually

Question 24

An inspector is testing the ground-fault monitoring circuit on the control panel. How does the inspector perform this test?

Options:

A.

Remove the primary power to the main control panel.

B.

Remove the signaling line circuit from the main control panel.

C.

Verify presence of a ground fault with a meter using the ohm scale.

D.

Verify the ground-fault indication when circuits are grounded.

Question 25

Which two of the following should occur when a signal silence switch for a notification alarm is activated? (Choose two.)

Options:

A.

Audible appliances are deactivated.

B.

Door holders are deactivated.

C.

HVAC shutdown is deactivated.

D.

Visible appliances are deactivated.

Page: 1 / 9
Total 85 questions