Winter Sale- Special Discount Limited Time 65% Offer - Ends in 0d 00h 00m 00s - Coupon code: netdisc

Exin CDCS EXIN EPI Certified Data Centre Specialist Exam Practice Test

Page: 1 / 12
Total 120 questions

EXIN EPI Certified Data Centre Specialist Questions and Answers

Question 1

EMF shielding material needs to be installed as EMF levels from the transformer room into the computer room are measured at 100 mG. The transformer room is ~10 meters away, separated by a corridor. Where should shielding be installed?

Options:

A.

It does not matter; either close to the transformer room or computer room is okay

B.

As close as possible to the transformer room

C.

As close as possible to the computer room

D.

Shielding is not required as 100 mG is within acceptable levels

Question 2

You need to determine the strategy for the cooling audit. All the servers are based on a front-to-rear (F-R) airflow design.

Which location for the temperature/humidity measurement should you recommend for the audit?

Options:

A.

At the back/rear of the server at 50 mm/2 inch

B.

At 1.5 meters/5 feet above the floor in the middle of the cold aisle

C.

At the front/intake of the server at 50 mm/2 inch

D.

At 1.5 meters/5 feet above the floor in the middle of the hot aisle

Question 3

What is the minimum requirement for the power feeds to the building for a Rated-3 data center based on the ANSI/TIA-942 standard?

Options:

A.

Two feeds coming from two different substations, one power company is not acceptable

B.

Two feeds coming from two different substations, one power company is acceptable

C.

Two feeds entering the data center building from one substation

D.

One feed from one substation split over two separated distribution boards in separate rooms

Question 4

Can you install a raised floor tight to the perimeter of the room?

Options:

A.

Yes, but only if the data center is located in Zone 0 with no or little seismic activity

B.

Yes, a raised floor needs to be installed tight to the perimeter to prevent air leakage

C.

No, to avoid damage to the raised floor due to building and hygrothermal movement

D.

No, but this applies only to raised floors with a height of over 90 cm (3 ft)

Question 5

An air-conditioner unit needs to be selected. Two types are available:

Unit-A has a Sensible Heat Ratio (SHR) of 0.7.

Unit-B has a Sensible Heat Ratio (SHR) of 0.9.

From an efficiency point of view, which one should be selected?

Options:

A.

It does not matter, as the Sensible Heat Ratio has nothing to do with efficiency.

B.

Not relevant, as Sensible Heat Ratio is only specified for air-conditioner equipment to indicate the ratio between intake temperature and exhaust temperature.

C.

Unit A

D.

Unit B

Question 6

Where should raised-floor installation start?

Options:

A.

Point A (entrance corner)

B.

Point B (side wall)

C.

Point C (center of the room)

D.

Point D (corner opposite entrance)

Question 7

A new facility requires electrical distribution of 100A to be installed in the computer room, 1 m (3 ft) above sensitive IT equipment. What type of system minimizes EMF impact?

Options:

A.

Install single-phase power cabling

B.

Install three-phase power cabling based on three individual core wires

C.

Install bus bar trunking

D.

Install three-phase power cabling based on a combined cable (e.g., XLPE)

Question 8

FM-200 is phasing out as a halocarbon gas and management has decided to replace this with the more environmentally friendly Novec-1230 gas. Should you use exactly the same formula and parameters to calculate the gas content for the Novec-1230 gas?

Options:

A.

Yes, as long as the temperature in the computer room has not changed

B.

Yes, if you take the difference between the net and gross volume into account

C.

Yes, as long as you use the same units of measure (kg/m³ or lbs/ft³)

D.

Yes, if you change the S-factor of the formula to reflect the gas type used

Question 9

What mainly affects the cooling capacity of a raised floor tile?

Options:

A.

Type of ICT equipment, location of the air conditioner, pressure under the raised floor, allowable temperature in the hot aisle

B.

Relative humidity in the computer room, temperature of the cold air, pressure under the raised floor, construction material of the tile

C.

Percentage of the surface opening, obstruction of the supporting construction, pressure under the raised floor, damper construction

D.

Percentage of the surface opening, airflow direction of the ICT equipment, temperature difference between the air intake and air exhaust of the ICT equipment, construction material of the tile

Question 10

You want to manage temperature and humidity only at the facility level in your data center. All servers use front-to-rear airflow. Which location for measurement should you recommend?

Options:

A.

At the back/rear of the server at 50 mm (2 in)

B.

At 1.5 m (5 ft) above the floor, 0.4 m (15 in) in front of the rack

C.

At the front/intake of the server at 50 mm (2 in)

D.

At 1.5 m (5 ft) above the floor, 0.4 m (15 in) at the back of the rack

Question 11

What is forced entry resistance based on?

Options:

A.

Time, tools, and people

B.

Rate and installed number of CCTV cameras

C.

Building materials used and the location of the data center

D.

The number of security guards on duty

Question 12

The air intake of the mission-critical server at the top of the rack is measuring 25 °C/77 °F.

Is this acceptable?

Options:

A.

Yes, this is allowed according to the standards and guidelines

B.

As long as it does not exceed the average server room temperature of 38 °C/100 °F

C.

Depends on the ANSI/TIA-942 Rating the data center needs to comply with

D.

No, the temperature needs to be 20 °C/68 °F

Question 13

Two servers stacked with no gap (metal-to-metal). What heat transfer occurs?

Options:

A.

No heat transfer

B.

Conduction

C.

Radiation

D.

Convection

Question 14

A data center scores Rated-3 in mechanical, Rated-4 in electrical, and Rated-2 in architectural.

What is the overall Rating of this data center when the Rating is based on the ANSI/TIA-942?

Options:

A.

Rated-2 since that is the lowest rating received

B.

Rated-4 since that is the highest rating received

C.

Rated-4 since electrical is more important than mechanical and architectural

D.

Depends on the Rating scored in telecommunications

Question 15

What is the main advantage of using an End-of-Row (EoR) design?

Options:

A.

A single Top-of-Rack (ToR) switch is more expensive than an EoR switch

B.

You need a separate rack to install all your EoR switches

C.

There will be fewer switches to manage (corrected typing: original said “more”)

D.

A ToR switch has only optical interfaces

Question 16

Do all residual current devices (RCDs) use the same operating principle?

Options:

A.

Yes, they all detect current differences on live and neutral wire

B.

Yes, they all measure voltage on the earth conductor

C.

No, ELCB measures earth voltage, whereas RCD detects current differences

D.

No, depending on regulations some use thermal-magnetic operation

Question 17

The temperature in the computer room is increased from 18 °C (64 °F) to 27 °C (81 °F). What is the impact on the amount of gas required to suppress a fire assuming a halocarbon agent?

Options:

A.

The amount of gas required will be higher

B.

The amount of gas required will not change

C.

The amount of gas required will be less

D.

The change cannot be determined without knowing the change in humidity as well

Question 18

The computer room has high levels of H2S gas contamination. What is the best option to resolve this issue?

Options:

A.

Vacuum the whole room using a HEPA/S-Class-based filter.

B.

Install air-scrubbers.

C.

Clean the room and racks with a damp/wet cloth.

D.

Provide more air changes per hour by adding more fresh air to the computer room.

Question 19

Do you need to consider bullet (ballistics) protection when designing a data center?

Options:

A.

Bullet (ballistics) protection is required by ANSI/TIA-942 for all data centers.

B.

Bullet (ballistics) protection is only required when the data center is located in an area with a high crime rate.

C.

Bullet (ballistics) protection is required by ANSI/TIA-942 for data centers Rated 3/4.

D.

Bullet (ballistics) protection is only required if the facility is a potential target or the building is in the vicinity of a potential target.

Question 20

Racks with 1.0 m depth and cold aisle containment with 3 perforated tiles are used. What aisle pitch is recommended?

Options:

A.

5 tiles pitch rule

B.

7 tiles pitch rule

C.

8 tiles pitch rule

D.

10 tiles pitch rule

Question 21

What should be implemented when an Inergen-based fire suppression system is installed in the computer room?

Options:

A.

Drainage system under raised floor

B.

Gas tanks need to be within or close to the data center

C.

Pressure release valves in the data center

D.

Proper water leak detection system

Question 22

The humidity in the computer room has increased from about 60% up to 85% Relative Humidity (RH). What potential risk does this pose to your equipment?

Options:

A.

No risks at all

B.

The risk of excessive wear and corrosion will increase

C.

The electrostatic discharge (ESD) levels will go up

D.

There will be a cooling risk due to a high wet bulb temperature

Question 23

Where should perforated tiles be installed?

Options:

A.

At the back of racks

B.

Every 5th rack

C.

One tile per rack in front

D.

As close to AC as possible

Question 24

From the options indicated, what is the correct starting point for the raised floor installation?

Question # 24

Options:

A.

Point A

B.

Point B

C.

Point C

D.

Point D

Question 25

Do you need to consider blast protection when designing a data center?

Options:

A.

No, there is no reason for implementing blast protection as nobody can predict the impact of a bomb explosion.

B.

Yes, if the data center is a potential target or the building is located within the vicinity of (close by) a potential target.

C.

No, blast protection is not a requirement of ANSI/TIA-942.

D.

Yes, blast protection is a requirement of ANSI/TIA-942.

Question 26

When are the wet bulb and dry bulb temperatures identical?

Options:

A.

When the dry bulb's temperature is at the lowest allowable temperature for IT equipment as per ASHRAE

B.

When the dry bulb's temperature is at the highest allowable temperature for IT equipment as per ASHRAE

C.

When the relative humidity is at the best practice value for relative humidity, being 50% RH

D.

When the relative humidity is 100%

Question 27

A data center has its own power supply from the public utility and receives chilled water supply from the building owner.

What needs to be taken into consideration when calculating the PUE?

Options:

A.

Nothing, as the chiller plant in the building also uses electrical power

B.

You will need to take the value for COP of the chiller plant into consideration

C.

You will need to take a weight factor of 0.4 for district chilled water into consideration

D.

PUE calculations are not possible in shared buildings

Question 28

A sprinkler system employs automatic sprinklers attached to a piping system containing water and connected to a water supply so that water discharges immediately when a head opens. What is this called?

Options:

A.

Dry pipe system

B.

Deluge system

C.

Pre-action system

D.

Wet pipe system

Question 29

It is assumed that EMF shielding material must be installed as the EMF levels coming from the transformer room into the computer room are measured at 100mG. The transformer room is approximately 10 meters away from the computer room and is separated by a corridor. You can assume that no physical issues are present for installing shielding material at any area/location.

Where should you recommend the shielding material to be installed?

Options:

A.

As close as possible to the computer room

B.

As close as possible to the transformer room

C.

It does not matter, either close to the transformer room or the computer room is okay as there is no impact to cost or shielding material performance

D.

Shielding is not required to be installed as 100mG is within the acceptable levels for computer rooms

Question 30

An MCB needs to be installed in the PDU of an ICT rack. Which breaking curve should you select?

Options:

A.

D-Curve

B.

C-Curve

C.

B-Curve

D.

A-Curve

Question 31

Smoke sensors must be installed in the computer room. What is the minimum density?

Options:

A.

1 per 5 m²

B.

1 per 10 m²

C.

1 per 25 m²

D.

1 per 40 m²

Question 32

Should aerosol cleaning solutions be used in the computer room?

Options:

A.

No, unless leak detection installed

B.

No, it will contaminate the room

C.

Yes, only if room smells bad

D.

Yes, if not connected to power

Question 33

What is the calculation for the desired attenuation factor for shielding material?

Options:

A.

A = 20 log (M / R)

Where

A is Attenuation

M is the maximum acceptable value

R is the real value measured

B.

A = M / R

Where

C.

A is Attenuation

M is the maximum acceptable value

R is the real value measured

D.

A = 20 log (R / M)

Where

A is Attenuation

R is the real value measured

M is the maximum acceptable value

E.

You do not have to calculate the attenuation factor for shielding material as it always has the same attenuation

Question 34

Which efficiency indicator accounts for all cooling costs (installation, operation, disposal)?

Options:

A.

HER

B.

COP

C.

PUE

D.

LCC

Question 35

In which stage of the data center life cycle does commissioning take place?

Options:

A.

Retire

B.

Operate/optimize

C.

Implement

D.

Design

Question 36

Does hot/cold aisle containment impact PUE?

Options:

A.

Yes, but not with cooling towers

B.

Yes, avoidance of mixing improves PUE

C.

No, airflow has no impact on power

D.

No, unless using virtualization

Page: 1 / 12
Total 120 questions